https://backend.automatara.com/media/catalog/product/cache/2697d6da213158f282a1a054727589d1/m/e/metsepm5760_67.jpg
PM5760 Meter, 2 ethernet, up to 63th H, 1,1M, wave+RCM, 4DI/2DO 52 alarms - METSEPM5760
METSEPM5760

0

(0 Reviews)

Description:

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.2S accuracy per IEC 62053-22 standard and 128 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to the 63rd Harmonic. Include 1.1 MegaBytes of memory for up to 14 selectable parameters with configurable interval and duration. This meter also feature the direct monitoring of neutral current, a residual current monitoring with ground current calculation plus an advanced waveform capture with sag and swell detection. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 480 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 20 to 690 VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 45 to 65 Hz. Communication protocol are Modbus RTU and ASCII 2 wires with RS485 port support plus Modbus TCP/IP, Ethernet/IP and BACnet/IP based on 10/100 Mbit/s, daisy chain Ethernet with RJ45 port support. The embedded communication capabilities allow the support of the DNP 3.0 protocol, the access to an onboard web server and a Serial to Ethernet gateway. The meter also has four digital inputs with WAGES support and two digital outputs. There are 52 configurable alarms and it supports eight tariff schedules. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 3.03 inches (77 millimetres), height 3.78 inches (96 millimetres) and product weight 15.9 onces (450 g).

Pre order time : 30 days

Rp 22.860.200
Pre Order
Characteristics
Documentation
Review
Main

product or component type

power meter

range

PowerLogic

device short name

PM5760

market segment

buildings large building cost management: billing: main incomer, buildings large building cost management: billing: sub feeder, buildings large building cost management: cost allocation: main incomer, buildings large building cost management: cost allocation: sub feeder, buildings large building network management: sub feeder, buildings medium building cost management: billing: main incomer, buildings medium building cost management: billing: sub feeder, buildings medium building cost management: cost allocation: main incomer, buildings medium building cost management: cost allocation: sub feeder, buildings medium building network management: main incomer, buildings medium building network management: sub feeder, buildings multi-site cost management: billing: main incomer, buildings multi-site cost management: billing: sub feeder, buildings multi-site cost management: cost allocation: main incomer, buildings multi-site cost management: cost allocation: sub feeder, buildings multi-site network management: sub feeder, buildings small building cost management: billing: main incomer, buildings small building cost management: billing: sub feeder, buildings small building cost management: cost allocation: main incomer, buildings small building cost management: cost allocation: sub feeder, buildings small building network management: main incomer, buildings small building network management: sub feeder, datacenter cost management: billing: main incomer, datacenter cost management: billing: sub feeder, datacenter cost management: cost allocation: main incomer, datacenter cost management: cost allocation: sub feeder, datacenter network management: sub feeder, healthcare cost management: billing: main incomer, healthcare cost management: billing: sub feeder, healthcare cost management: cost allocation: main incomer, healthcare cost management: cost allocation: sub feeder, healthcare network management: sub feeder, industry cost management: billing: main incomer, industry cost management: billing: sub feeder, industry cost management: cost allocation: main incomer, industry cost management: cost allocation: sub feeder, industry network management: sub feeder

product name

PowerLogic PM5000